RTD Converter KFD0-TR-Ex1, 1-ch. isolated barrier, input 2/3wire Pt100, output 4..20mA, selec. temperature linearization, DIP switch selectable ranges, sensor breakage detection, sv 24VDC loop powered, Pepperl+Fuchs Code:
043691
Price (indicative)
€199.30
/pc
(€243.15 /pc with VAT)
Manufacturer
:
Availability:
21 days
|
Weight:
0.1575 kg/pc
|
Volume:
0.0003 m3/pc
|
|
|
|
|
RTD Converter KFD0-TR-Ex1, 1-ch., input 2-/3-wire PT100/RTD, output 4..20mA, DIP switch selectable ranges, ATEX, 24VDC LP, Pepperl+FuchsRTD Converter KFD0-TR-Ex1
- 1-channel isolated barrier
- 24 V DC supply (loop powered)
- 2- or 3-wire Pt100 RTD input
- Output 4 mA ... 20 mA, temperature linearization selectable
- DIP switch selectable ranges
- Sensor breakage detection
Datasheet excerpt: Technical data of KFD0-TR-Ex1
General specifications |
Signal type | Analog input |
Supply |
Rated voltage | 12 ... 35 V DC loop powered |
Power dissipation | 0.4 W |
Input |
Connection side | field side |
Connection | terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection |
Lead resistance | max. 100 Ω per line |
Measuring current | approx. 1 mA |
Output |
Connection side | control side |
Connection | terminals 9+, 8- |
Load | (U -12 V) / 0.02 A |
Current output | 4 ... 20 mA , limited to ≤ 35 mA |
Fault signal | upscaling ≥ 22 mA (limited to 35 mA) |
Transfer characteristics |
Measurement range | span without linearization 25 ... 800 °C (77 ... 1472 °F)/with linearization 25 ... 375 °C (77 ... 707 °F), both adjustable zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/with linearization -30 ... 375 °C (-22 ... 707 °F), both adjustable |
Rise time | 250 ms |
Indicators/settings |
Control elements | DIP-switch rotary switch |
Configuration | via DIP switches via rotary switch |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Insulation coordination | EN 50178 |
Galvanic isolation | EN 50178 |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | ZELM 00 ATEX 0036 |
| Marking | II (1)GD [EEx ia] IIC |
Certificate | TÜV 01 ATEX 1777 X |
| Marking | II 3G Ex nA II T4 |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
CSA approval | |
| Control drawing | 116-0132 |
|
|
|
|
|