Image is illustrative
|
Temperature Sensor ThermasGard® ATM2-Modbus, Pt1000, -50..150°C, 24VAC/15..36VDC, M16x1.5, calibratable, IP65, S+S Regeltechnik Code:
1101-1246-0000-000
Price
€131.50
/pc
(€160.43 /pc with VAT)
Manufacturer
:
Availability:
14 days
|
Weight:
0.03 kg/pc
|
|
|
|
|
|
Outside temperature transducers THERMASGARD® ATM2-Modbus, Pt1000, -50..150°C, 24VAC/15..36VDC, M16x1.5, IP65, calibratable, S+S Regeltechnik
Calibratable outside temperature measuring transducer with internal or external sensor THERMASGARD® ATM 2 - Modbus with Modbus connection, terminal box enclosure made of impact-resistant plastic, enclosure cover with quick-locking screws, with ⁄ without optional display indicating the actual temperature.
It is used to detect outside temperatures, temperatures in wet rooms e.g. for installation on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas preferably at the north side of a building or in a protected place. In case of direct sun irradiation, the sunshade and ball game protection WS 01 (accessories) or the device variant with the installed sunshade SS 02 (available on request) must be used. The outdoor sensors are factory-calibrated. Adjustment ⁄ fine adjustment by the user is possible (zero point offset is adjustable).
|
|
Technical data:
|
Power supply: |
24 V AC ±10%
15...36 V DC |
Power consumption: |
< 2.2 VA / 24 V AC
< 1.1 W / 24 V DC |
Temperature-measuring range: |
-50 ... 150 °C |
Deviation, temperature: |
±0.8 K, ± 0,2 K bei +25 °C |
Operation range, temperature: |
-30 ... 70 °C |
Operation range, humidity: |
0 ... 95 %r.H. non-precipitating air |
Storage temperature: |
-30 ... 70 °C |
Enclosure dimensions: |
72 x 64 x 37.8 mm (Tyr 1) |
lectrical connection: |
0.14 - 1.5 mm², 5-wire connection, via terminal screws on circuit board |
|
|
|
|
|