Image is illustrative
|
Safety Rated Analog Input Module PointGuard I/O, in-cabinet, 4-ch., Allen-Bradley Code:
1734-IE4S
Price (indicative)
€922.20
/pc
(€1,125.08 /pc with VAT)
Manufacturer
:
Availability:
21 days
|
Weight:
0.0856 kg/pc
|
Volume:
0 m3/pc
|
|
|
|
|
Safety Rated Analog Input Module PointGuard I/O, in-cabinet, 4-ch., Allen-Bradley
DESCRIPTIONS
-
POINTGuard I/O™ Safety Rated Analog Input Module, Type: In-Cabinet, Number Of Channels: 4 (Single-Ended, Non-Isolated), Input: Voltage Mode: 0 - 10 V, 0 - 5 V, Plus/Minus 5 V, Plus/Minus 10 V, Current Mode: 0 - 20 MA, 4 - 20 MA, Tachometer Mode: 0 - 24 V, Field Power Input: 19.2 - 28.8 VDC, 65 MA, Output: 24 VDC Sensor, 150 MA Per Output At 55 DEG C, On-State Voltage: Less Than Or Equal To 0.5 V, Leakage: Less Than: 0.1 MA, Enclosure: Open Type, Mounting: DIN Rail, Length: 0.98 IN, Width: 2.17 IN, Height: 3.03 IN, Temperature Rating: -20 To 55 DEG C, Environmental Conditions: 5 - 95% Non-Condensing Relative Humidity, Shock: 30 G Operating, 50 G Nonoperating, Vibration: 5 G At 10 - 500 HZ, Accuracy: Voltage: Plus/Minus 0.5% Full Scale At 25 DEG C, Current Mode: Plus/Minus 0.6% Full Scale At 25 DEG C, Tachometer Mode: Plus/Minus 2% At 25 DEG C, I/O Scan Rate: Greater Than Or Equal To 6 MS, Input Step Response: 450 MS At 1 HZ Frequency, 25 MS At 50 HZ Filter Frequency, Impedance: Voltage Mode: Greater Than 200 KOHM(Input), Current Mode: Less Than 100 OHM, Tachometer Mode: Greater Than 200 KOHM, Resolution: 12 Bits, Rejection Ratio: Normal Mode: 70 DB At 60 HZ For 1 HZ Filter Frequency, 70 DB At 60 HZ For 5 HZ Filter Frequency, 50 DB At 60 HZ For 10 HZ Filter Frequency, 20 DB At 60 HZ For 10 HZ Filter Frequency, Standard/Approvals: CE-ATEX marked, CE-EMC marked, C-Tick certified, KCC certified, ROSTECHNADZOR certified, UL-CA listed, UL-CA_HAZ listed, UL-US listed, UL-US_HAZ listed, Application: For use with GuardLogix controller
SPECIFICATIONS
-
-
Item Name: Safety Rated Analog Input Module
-
Type: In-Cabinet
-
Sub Brand: POINTGuard I/O™
-
Number Of Channels: 4 (Single-Ended, Non-Isolated)
-
Input: Voltage Mode: 0 - 10 V, 0 - 5 V, Plus/Minus 5 V, Plus/Minus 10 V, Current Mode: 0 - 20 MA, 4 - 20 MA, Tachometer Mode: 0 - 24 V, Field Power Input: 19.2 - 28.8 VDC, 65 MA
-
Output: 24 VDC Sensor, 150 MA Per Output At 55 DEG C, On-State Voltage: Less Than Or Equal To 0.5 V, Leakage: Less Than: 0.1 MA
-
Enclosure: Open Type
-
Mounting: DIN Rail
-
Length: 0.98 IN
-
Width: 2.17 IN
-
Height: 3.03 IN
-
Temperature Rating: -20 To 55 DEG C
-
Environmental Conditions: 5 - 95% Non-Condensing Relative Humidity, Shock: 30 G Operating, 50 G Nonoperating, Vibration: 5 G At 10 - 500 HZ
-
Accuracy: Voltage: Plus/Minus 0.5% Full Scale At 25 DEG C, Current Mode: Plus/Minus 0.6% Full Scale At 25 DEG C, Tachometer Mode: Plus/Minus 2% At 25 DEG C
-
Resolution: 12 Bits
-
Impedance: Voltage Mode: Greater Than 200 KOHM(Input), Current Mode: Less Than 100 OHM, Tachometer Mode: Greater Than 200 KOHM
-
Input Step Response: 450 MS At 1 HZ Frequency, 25 MS At 50 HZ Filter Frequency
-
Rejection Ratio: Normal Mode: 70 DB At 60 HZ For 1 HZ Filter Frequency, 70 DB At 60 HZ For 5 HZ Filter Frequency, 50 DB At 60 HZ For 10 HZ Filter Frequency, 20 DB At 60 HZ For 10 HZ Filter Frequency
-
I/O Scan Rate: Greater Than Or Equal To 6 MS
FEATURES
-
- Cost savings modular design requires less enclosure space
- Up to 504 channels on a single network interface
- Removable terminations accelerate commissioning
- Remove and insert under power reduces maintenance time
- Local autonomous control
- Fast, simple configuration and integration
- Full Add-on-Profiles in RSLogix 5000, no other software is needed
- Channel-level diagnostics
- Greater flexibility
- Local control
- Controlled by a single GuardLogix controller
- Over current detection
- Open load detection
- Single pole anti aliasing filter
- Standards: CE-ATEX marked, CE-EMC marked, C-Tick certified, KCC certified, ROSTECHNADZOR certified, UL-CA listed, UL-CA_HAZ listed, UL-US listed, UL-US_HAZ listed
- Applications: For use with GuardLogix controller
|
|
|
|