Image is illustrative
|
Redundancy Module QUINT-ORING/24DC/2X10/1X20, protective coating, Phoenix Code:
2320173
Price
€310.20
/pc
(€378.44 /pc with VAT)
Manufacturer
:
Availability:
21 days
|
Weight:
0.6343 kg/pc
|
Volume:
0.0018 m3/pc
|
|
|
|
|
Redundancy Module QUINT-ORING/24DC/2X10/1X20, protective coating, PhoenixDimensions
Width
|
32 mm
|
Height
|
130 mm
|
Depth
|
125 mm
|
Width with alternative assembly
|
122 mm
|
Height with alternative assembly
|
130 mm
|
Depth with alternative assembly
|
35 mm
|
Installation distance right/left
|
5 mm / 5 mm
|
Installation distance top/bottom
|
50 mm / 50 mm
|
Ambient conditions
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 100 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Installation height
|
2000 m
|
Input data
Nominal input voltage range
|
24 V DC
|
Input voltage range
|
18 V DC ... 28 V DC (SELV)
|
Nominal input current
|
2x 10 A (-25 °C ... 60 °C)
|
|
1x 20 A (-25 °C ... 60 °C)
|
Maximum input current
|
2x 15 A (-25°C ... 40°C)
|
|
1x 30 A (-25°C ... 40°C)
|
|
60 A (12 ms, SFB Technology)
|
Output data
Nominal output voltage
|
0.1 V (< DC input)
|
Nominal output current (IN)
|
20 A (Increasing power)
|
|
10 A (Redundancy)
|
Derating
|
60 °C ... 70 °C (2.5%/K)
|
Connection in series
|
No
|
Protection against overvoltage at the output (OVP)
|
≤ 32 V DC
|
Power loss nominal load max.
|
2 W (IOUT = 20 A)
|
General
Net weight
|
0.4 kg
|
Efficiency
|
> 98 %
|
MTBF (IEC 61709, SN 29500)
|
> 1000000 h (40 °C)
|
Degree of protection
|
IP20
|
Protection class
|
III
|
Housing material
|
Steel sheet, zinc-plated
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
|
Connection data, input
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
4 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
14
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
8 mm
|
Screw thread
|
M3
|
Connection data, output
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
10
|
Stripping length
|
7 mm
|
Screw thread
|
M3
|
Connection data for signaling
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
4 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
16
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
10 mm
|
Screw thread
|
M3
|
Standards
EMC requirements for noise immunity
|
EN 61000-6-1
|
|
EN 61000-6-2
|
EMC requirements for noise emission
|
EN 61000-6-3
|
|
EN 61000-6-4
|
Standard - Electrical safety
|
EN 60950-1/VDE 0805 (SELV)
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
Standard – Safety extra-low voltage
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
Conformance/approvals
UL approvals
|
UL/C-UL listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
EMC data
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Low Voltage Directive
|
Conformance with Low Voltage Directive 2014/35/EC
|
Electrostatic discharge
|
EN 61000-4-2
|
Contact discharge
|
8 kV (Test Level 4)
|
Discharge in air
|
15 kV (Test Level 4)
|
Electromagnetic HF field
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
20 V/m (Test Level 3)
|
Frequency range
|
1 GHz ... 2 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
2 GHz ... 3 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Comments
|
Criterion A
|
Fast transients (burst)
|
EN 61000-4-4
|
Input
|
2 kV (Test Level 3 - asymmetrical)
|
Output
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
2 kV (Test Level 4 - asymmetrical)
|
Comments
|
Criterion B
|
Surge voltage load (surge)
|
EN 61000-4-5
|
Input
|
1 kV (Test Level 2 - symmetrical)
|
|
2 kV (Test Level 3 - asymmetrical)
|
Output
|
1 kV (Test Level 2 - symmetrical)
|
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
1 kV (Test Level 2 - asymmetrical)
|
Comments
|
Criterion B
|
Conducted interference
|
EN 61000-4-6
|
I/O/S
|
asymmetrical
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Comments
|
Criterion A
|
Criterion A
|
Normal operating behavior within the specified limits.
|
Criterion B
|
Temporary impairment to operational behavior that is corrected by the device itself.
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27371010
|
ECLASS 11.0 |
27371010
|
ECLASS 4.0 |
27250300
|
ECLASS 4.1 |
27250300
|
ECLASS 5.0 |
27371000
|
ECLASS 5.1 |
27371000
|
ECLASS 6.0 |
27371000
|
ECLASS 7.0 |
27371010
|
ECLASS 9.0 |
27371010
|
ETIM
ETIM 3.0 |
EC000599
|
ETIM 4.0 |
EC000599
|
ETIM 6.0 |
EC000683
|
ETIM 7.0 |
EC000683
|
UNSPSC
UNSPSC 6.01 |
30211502
|
UNSPSC 7.0901 |
39121004
|
UNSPSC 11 |
39121004
|
UNSPSC 12.01 |
39121004
|
UNSPSC 13.2 |
32151504
|
UNSPSC 18.0 |
32151504
|
UNSPSC 19.0 |
32151504
|
UNSPSC 20.0 |
32151504
|
UNSPSC 21.0 |
32151504
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|