Image is illustrative
|
Temperature Repeater KCD2-RR-Ex1, 1-ch. isolated barrier, 24VDC PR, resistance and RTD input (Pt100/Pt500/Pt1000), resistance output, accuracy 0.1%, LFD, SIL2, Pepperl+Fuchs Code:
258075
Price (indicative)
€390.00
/pc
(€475.80 /pc with VAT)
Manufacturer
:
Availability:
21 days
|
Weight:
0.1234 kg/pc
|
|
|
|
|
|
Temperature Repeater KCD2-RR-Ex1, 1-ch. isolated barrier, 24VDC PR, resistance and RTD input (Pt100/Pt500/Pt1000), resistance output, accuracy 0.1%, LFD, SIL2, Pepperl+Fuchs
This isolated barrier is used for intrinsic safety applications. It transfers resistance values of RTDs or potentiometers from hazardous areas to safe areas. A 2-, 3-, or 4-wire technique is available depending on the required accuracy. The input card of the control system measures the same load as if it were connected directly to the resistance in a hazardous
area.
|
|
|
General specifications:
|
Signal type: |
Analog input |
Supply:
|
Connection: |
Power Rail or terminals 9+, 10- |
Rated voltage: |
19 ... 30 V DC |
Ripple: |
within the supply tolerance |
Rated current: |
< 20 mA |
Power consumption: |
0.35 W (24 V and 1 mA sense current) |
Input:
|
Connection: |
terminals 1, 2, 3, 4 |
Line fault detection: |
yes , at Pt100 |
Lead resistance: |
≤ 10 % of resistance value |
Transmission range: |
0 ... 10 mA |
Available voltage: |
9 V |
Line fault detection: |
8 nA |
Output:
|
Connection: |
terminals 5-, 7-, 6+, 8+ |
Current: |
0 ... 10 mA |
Available voltage: |
0 ... 4.2 V |
Fault signal: |
< 10 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1mA) |
Mechanical specifications:
|
Degree of protection: |
IP20 |
Mass: |
approx. 100 g |
Dimensions: |
12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 |
Mounting: |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
|
File description
|
File type
|
Download link
|
|
|
|
Product data sheet
|
PDF
|
Download link
|
|
|
|
|
|