|
|
|
Image is illustrative
|
Signal Conditioner MINI MCR-SL-I-I, Phoenix Code:
2864406
Price
€227.40
/pc
(€277.43 /pc with VAT)
Manufacturer
:
Availability:
28 days
|
Weight:
0.0747 kg/pc
|
Volume:
0.0001 m3/pc
|
|
|
|
|
Signal Conditioner MINI MCR-SL-I-I, PhoenixNote
Utilization restriction
|
EMC: class A product, see manufacturer's declaration in the download area
|
Dimensions
Width
|
6.2 mm
|
Height
|
93.1 mm
|
Depth
|
101.2 mm
|
Ambient conditions
Ambient temperature (operation)
|
-20 °C ... 65 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Maximum altitude
|
≤ 2000 m
|
Permissible humidity (operation)
|
5 % ... 95 % (non-condensing)
|
Degree of protection
|
IP20
|
Noise immunity
|
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
|
Input data
Number of inputs
|
1
|
Configurable/programmable
|
no
|
Current input signal
|
0 mA ... 20 mA
|
|
4 mA ... 20 mA
|
Max. input current
|
50 mA
|
Input resistance current input
|
approx. 50 Ω
|
Output data
Number of outputs
|
1
|
Configurable/programmable
|
no
|
Current output signal
|
0 mA ... 20 mA
|
|
4 mA ... 20 mA
|
Max. output current
|
28 mA
|
Load/output load current output
|
< 500 Ω (at 20 mA)
|
Ripple
|
< 20 mVPP (at 500 Ω)
|
Power supply
Nominal supply voltage
|
24 V DC
|
Supply voltage range
|
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
|
Max. current consumption
|
< 20 mA
|
Power consumption
|
< 450 mW
|
Connection data
Connection method
|
Screw connection
|
Stripping length
|
12 mm
|
Screw thread
|
M3
|
Conductor cross section solid
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section AWG
|
26 ... 12
|
General
No. of channels
|
1
|
Maximum transmission error
|
≤ 0.1 % (of final value)
|
Maximum temperature coefficient
|
< 0.01 %/K
|
Temperature coefficient, typical
|
< 0.002 %/K
|
Limit frequency (3 dB)
|
approx. 100 Hz
|
Step response (10-90%)
|
approx. 3.2 ms
|
Protective circuit
|
Transient protection
|
Electrical isolation
|
Basic insulation according to EN 61010
|
Overvoltage category
|
II
|
Degree of pollution
|
2
|
Rated insulation voltage
|
50 V AC/DC
|
Test voltage, input/output/supply
|
1.5 kV (50 Hz, 1 min.)
|
Electromagnetic compatibility
|
Conformance with EMC directive
|
Noise emission
|
EN 61000-6-4
|
Noise immunity
|
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
|
Color
|
green
|
Housing material
|
PBT
|
Mounting position
|
any
|
Assembly instructions
|
The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
|
Fire protection for rail vehicles (DIN EN 45545-2) R22
|
HL 1 - HL 2
|
Fire protection for rail vehicles (DIN EN 45545-2) R23
|
HL 1 - HL 2
|
Fire protection for rail vehicles (DIN EN 45545-2) R24
|
HL 1 - HL 2
|
EMC data
Designation
|
Electromagnetic RF field
|
Standards/regulations
|
EN 61000-4-3
|
Typical deviation from the measuring range final value
|
10 %
|
Designation
|
Fast transients (burst)
|
Standards/regulations
|
EN 61000-4-4
|
Typical deviation from the measuring range final value
|
10 %
|
Designation
|
Conducted interferences
|
Standards/regulations
|
EN 61000-4-6
|
Typical deviation from the measuring range final value
|
10 %
|
Standards and Regulations
Electromagnetic compatibility
|
Conformance with EMC directive
|
Noise emission
|
EN 61000-6-4
|
Connection in acc. with standard
|
CUL
|
Designation
|
Electromagnetic RF field
|
Standards/regulations
|
EN 61000-4-3
|
|
EN 61000-4-4
|
Designation
|
Conducted interferences
|
Standards/regulations
|
EN 61000-4-6
|
Electrical isolation
|
Basic insulation according to EN 61010
|
Conformance/approvals
Designation
|
CE
|
Certificate
|
CE-compliant
|
Designation
|
UL, USA/Canada
|
Identification
|
UL 508 Recognized
|
|
Class I, Div. 2, Groups A, B, C, D T5
|
Designation
|
Shipbuilding approval
|
Certificate
|
DNV GL TAA000020N
|
Temperature
|
B
|
Humidity
|
B
|
Vibration
|
B
|
EMC
|
A
|
Enclosure
|
Required protection according to the Rules shall be provided upon installation on board
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 50 years
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27210120
|
ECLASS 11.0 |
27210120
|
ECLASS 4.0 |
27210100
|
ECLASS 4.1 |
27210100
|
ECLASS 5.0 |
27210100
|
ECLASS 5.1 |
27210100
|
ECLASS 6.0 |
27210100
|
ECLASS 7.0 |
27210120
|
ECLASS 9.0 |
27210120
|
ETIM
ETIM 4.0 |
EC002653
|
ETIM 6.0 |
EC002653
|
ETIM 7.0 |
EC002653
|
UNSPSC
UNSPSC 6.01 |
30211506
|
UNSPSC 7.0901 |
39121008
|
UNSPSC 11 |
39121008
|
UNSPSC 12.01 |
39121008
|
UNSPSC 13.2 |
39121008
|
UNSPSC 18.0 |
39121008
|
UNSPSC 19.0 |
39121008
|
UNSPSC 20.0 |
39121008
|
UNSPSC 21.0 |
39121008
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|