Safety Relay PSR-SCP-24UC/ESA2/4X1/1X2/B, Phoenix Code:
2963802
Price
€254.20
/pc
(€310.12 /pc with VAT)
Manufacturer
:
Availability:
21 days
|
Weight:
0.221 kg/pc
|
Volume:
0.0004 m3/pc
|
|
|
|
|
Safety Relay PSR-SCP-24UC/ESA2/4X1/1X2/B, PhoenixNote
Utilization restriction
|
EMC: class A product, see manufacturer's declaration in the download area
|
Dimensions
Width
|
22.5 mm
|
Height
|
99 mm
|
Depth
|
114.5 mm
|
Ambient conditions
Ambient temperature (operation)
|
-20 °C ... 65 °C (observe derating)
|
Ambient temperature (storage/transport)
|
-40 °C ... 70 °C
|
Max. permissible relative humidity (operation)
|
75 % (on average, 85% infrequently, non-condensing)
|
Max. permissible humidity (storage/transport)
|
75 % (on average, 85% infrequently, non-condensing)
|
Maximum altitude
|
≤ 2000 m (Above sea level)
|
Input data
Rated control circuit supply voltage US
|
24 V AC/DC -15 % / +10 %
|
Rated control supply current IS
|
typ. 140 mA AC
|
|
typ. 65 mA DC
|
Power consumption at US
|
typ. 3.36 W (AC)
|
|
typ. 1.56 W (DC)
|
Inrush current
|
2 A (Δt = 10 ms at Us)
|
|
< 40 mA (with Us/Ix to S34)
|
Current consumption
|
< 50 mA (with Us/Ix to S12)
|
|
0 mA (with Us/Ix to S34)
|
Voltage at input/start and feedback circuit
|
24 V DC -15 % / +10 %
|
Typical response time
|
< 65 ms (automatic start)
|
|
< 40 ms (manual start)
|
Typ. starting time with Us
|
< 65 ms (when controlled via A1)
|
Typical release time
|
< 45 ms (when controlled via S12)
|
|
< 200 ms (when controlled via A1)
|
Recovery time
|
< 1 s
|
Operating voltage display
|
1 x green LED
|
Status display
|
2 x green LEDs
|
Protective circuit
|
Surge protection Suppressor diode
|
|
Protection against polarity reversal for rated control circuit supply voltage
|
Maximum switching frequency
|
1 Hz
|
Max. permissible overall conductor resistance
|
approx. 22 Ω (Input and start circuits at US)
|
Filter time
|
2 ms (at A1 in the event of voltage dips at Us)
|
|
max. 1.5 ms (at S12; test pulse width)
|
|
7.5 ms (at S12; test pulse rate)
|
|
Test pulse rate = 5 x Test pulse width
|
Output data
Contact type
|
4 enabling current paths
|
|
1 signaling current path
|
Contact material
|
AgSnO2
|
Maximum switching voltage
|
250 V AC/DC (Observe the load curve)
|
Minimum switching voltage
|
5 V AC/DC
|
Limiting continuous current
|
6 A (N/O contact, pay attention to the derating)
|
|
6 A (N/C contact)
|
Maximum inrush current
|
20 A (Δt 100 ms)
|
Inrush current, minimum
|
10 mA
|
Sq. Total current
|
72 A2 (observe derating)
|
Interrupting rating (ohmic load) max.
|
144 W (24 V DC, τ = 0 ms)
|
|
288 W (48 V DC, τ = 0 ms)
|
|
110 W (110 V DC, τ = 0 ms)
|
|
88 W (220 V DC, τ = 0 ms)
|
|
1500 VA (250 V AC, τ = 0 ms)
|
Maximum interrupting rating (inductive load)
|
42 W (24 V DC, τ = 40 ms)
|
|
42 W (48 V DC, τ = 40 ms)
|
|
42 W (110 V DC, τ = 40 ms)
|
|
42 W (220 V DC, τ = 40 ms)
|
Switching capacity min.
|
50 mW
|
Mechanical service life
|
10x 106 cycles
|
Switching capacity (360/h cycles)
|
4 A (24 V DC)
|
|
4 A (230 V AC)
|
Output fuse
|
10 A gL/gG (N/O contact)
|
|
6 A gL/gG (N/C contact)
|
General
Relay type
|
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
|
Nominal operating mode
|
100% operating factor
|
Net weight
|
210.5 g
|
Mounting position
|
vertical or horizontal
|
Mounting type
|
DIN rail mounting
|
Assembly instructions
|
See derating curve
|
Degree of protection
|
IP20
|
Min. degree of protection of inst. location
|
IP54
|
Housing material
|
Polyamide
|
Housing color
|
yellow
|
Connection data
Connection method
|
Screw connection
|
pluggable
|
Yes
|
Conductor cross section solid
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 2.5 mm²
|
Conductor cross-section AWG
|
24 ... 12
|
Stripping length
|
7 mm
|
Screw thread
|
M3
|
Safety-related characteristic data
Stop category in accordance with IEC 60204
|
0
|
Designation
|
IEC 61508 - High demand
|
Safety Integrity Level (SIL)
|
1 (up to SIL 3 depending on the application)
|
Designation
|
IEC 61508 - Low demand
|
Safety Integrity Level (SIL)
|
1 (up to SIL 3 depending on the application)
|
Designation
|
EN ISO 13849
|
Performance level (PL)
|
c (up to PL e depending on the application)
|
Category
|
1 (up to Cat. 4 depending on the application)
|
Designation
|
EN 62061
|
Safety Integrity Level Claim Limit (SIL CL)
|
1 (up to SILCL 3 depending on the application)
|
Standards and Regulations
Designation
|
Air clearances and creepage distances between the power circuits
|
Standards/regulations
|
DIN EN 50178/VDE 0160
|
Rated insulation voltage
|
250 V AC
|
Rated surge voltage/insulation
|
Basic insulation 4 kV: between all current paths and housing Safe isolation, reinforced insulation 6 kV: between A1/A2 and 13/14, 23/24, 33/34, 43/44 between S11/S12/S33/S34 and 13/14, 23/24, 33/34, 43/44 between 51/52 and 13/14, 23/24, 33/34, 43/44
|
Degree of pollution
|
2
|
Overvoltage category
|
III
|
Shock
|
15g
|
Vibration (operation)
|
10 Hz ... 150 Hz, 2g
|
Conformance
|
CE-compliant
|
Environmental Product Compliance
China RoHS
|
Environmentally Friendly Use Period = 50 years
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27371819
|
ECLASS 11.0 |
27371819
|
ECLASS 4.0 |
40020600
|
ECLASS 4.1 |
40020600
|
ECLASS 5.0 |
27371900
|
ECLASS 5.1 |
27371900
|
ECLASS 6.0 |
27371800
|
ECLASS 7.0 |
27371819
|
ECLASS 9.0 |
27371819
|
ETIM
ETIM 2.0 |
EC000196
|
ETIM 3.0 |
EC001449
|
ETIM 4.0 |
EC001449
|
ETIM 6.0 |
EC001449
|
ETIM 7.0 |
EC001449
|
UNSPSC
UNSPSC 6.01 |
30211901
|
UNSPSC 7.0901 |
39121501
|
UNSPSC 11 |
39121501
|
UNSPSC 12.01 |
39121501
|
UNSPSC 13.2 |
39121501
|
UNSPSC 18.0 |
39122205
|
UNSPSC 19.0 |
39122205
|
UNSPSC 20.0 |
39122205
|
UNSPSC 21.0 |
39122205
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|