Monitoring Safety Relay MSR138DP, delayed output single-function, input 1NC?2NC, output 2NO safety/ 3NO delayed safety| 6A 24VDC, 24VAC/VDC, TS35, Allen-Bradley
DESCRIPTIONS
-
Monitoring Safety Relay, Type: MSR138DP Series, Delayed Output Single-Function, Coil: 24 VAC/VDC, Contact Configuration: Input: 1NC, 2NC, Output: 2NO Safety, 3NO Delayed Safety, Contact Rating: 6 A At 24 VDC, Mounting: 35 MM DIN Rail, Resistance: 135 OHM, Enclosure: IP20, IP40, NEMA 1, Withstand Voltage: 2500 V, Size: 3.89 IN Height X 1.77 IN Width X 4-1/2 IN Depth, Operating Cycles: Mechanical: 2000000, Temperature Rating: -5 To 55 DEG C, Environmental Conditions: Vibration: 0.35 MM At 10 To 55 HZ, Shock: 10 G At 16 MS, 100 Shocks, Time Delay: 0.5 - 10 SEC, Input Simultaneity: Infinite, Reset Type: Automatic/Manual Or Monitored Manual
SPECIFICATIONS
-
-
Item Name: Monitoring Safety Relay
-
Type: MSR138DP Series, Delayed Output Single-Function
-
Coil: 24 VAC/VDC
-
Contact Configuration: Input: 1NC, 2NC, Output: 2NO Safety, 3NO Delayed Safety
-
Contact Rating: 6 A At 24 VDC
-
Mounting: 35 MM DIN Rail
-
Resistance: 135 OHM
-
Enclosure: IP20, IP40, NEMA 1
-
Withstand Voltage: 2500 V
-
Size: 3.89 IN Height X 1.77 IN Width X 4-1/2 IN Depth
-
Operating Cycles: Mechanical: 2000000
-
Temperature Rating: -5 To 55 DEG C
-
Environmental Conditions: Vibration: 0.35 MM At 10 To 55 HZ, Shock: 10 G At 16 MS, 100 Shocks
-
Reset Type: Automatic/Manual Or Monitored Manual
-
Input Simultaneity: Infinite
-
Time Delay: 0.5 - 10 SEC
FEATURES
-
The MSR138DP can be connected in 3 different input wiring configurations: 1 normally closed, 2 normally closed, or 2 OSSD. When connected in the two normally closed fashion, the MSR138DP checks for cross faults across the two inputs. When connected to light curtains, the light curtain must perform the cross-fault detection. The MSR138DP has output monitoring that can accommodate either automatic/manual reset or a monitored manual reset. When configured with automatic/manual reset (jumpers on X1-X2 and X3-X4), the MSR138DP can have the reset terminals S33-S34 jumpered or can be converted to an unmonitored manual reset by adding a normally open switch in the monitoring loop (S33-S34). When configured to monitored manual reset, the MSR138DP checks the output monitoring circuit through the manual application of the reset switch. The unit cannot be reset until the timing function has completed. The outputs of the MSR138DP include two normally open immediate safety outputs and three normally open delayed safety outputs. The outputs of the MSR138.1DP include two normally open immediate safety rated outputs, two normally open delayed safety outputs and one normally closed delayed safety output. The safety outputs have independent and redundant internal contacts to support the safety function. If a reset request is made during the time cycle, it will cause a lockout condition. Cycle inputs after timing has completed and reset after the delay time has expired to clear lockout. Connecting contacts 55-56 of the MSR138.1DP in series to Y1-Y2 can avoid this lockout. - Category 4/3 per EN 954-1
- Stop category 0 and 1
- Light curtain, E-stop, safety gate inputs
- Two immediate safety outputs
- Cross fault monitoring
- No auxiliary output
- Standards: CE marked, cULus listed, c-Tick marked, TUV certified