SITOP PSU100S 20 A Stabilized power supply input: 120/230 V AC, output: 24 V DC/20 A |
Input |
Input |
1-phase AC |
● Note |
Automatic range selection |
Supply voltage |
|
● 1 at AC Rated value |
120 V |
● 2 at AC Rated value |
230 V |
Input voltage |
|
● 1 at AC |
85 ... 132 V |
● 2 at AC |
176 ... 264 V |
Wide-range input |
No |
Overvoltage resistance |
2.3 × Vin rated, 1.3 ms |
Mains buffering |
at Vin = 120/230 V |
Mains buffering at Iout rated, min. |
20 ms; at Vin = 120/230 V |
Rated line frequency 1 |
50 Hz |
Rated line frequency 2 |
60 Hz |
Rated line range |
47 ... 63 Hz |
Input current |
|
● at rated input voltage 120 V |
7.5 A |
● at rated input voltage 230 V |
3.5 A |
Switch-on current limiting (+25 °C), max. |
11 A |
I²t, max. |
10 A²·s |
Built-in incoming fuse |
T 10 A (not accessible) |
Protection in the mains power input (IEC 898) |
Recommended miniature circuit breaker: from 10 A characteristic C or circuit-breaker 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230 V) |
Output |
Output |
Controlled, isolated DC voltage |
Rated voltage Vout DC |
24 V |
Total tolerance, static ± |
3 % |
Static mains compensation, approx. |
0.5 % |
Static load balancing, approx. |
1 % |
Residual ripple peak-peak, max. |
150 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) |
240 mV |
Adjustment range |
24 ... 28 V |
Product function Output voltage adjustable |
Yes |
Output voltage setting |
via potentiometer; max. 480 W |
Status display |
Green LED for 24 V OK |
Signaling |
Relay contact (NO contact, rating 50 V DC/ 0.3 A) for "24 V OK" |
On/off behavior |
No overshoot of Vout (soft start) |
Startup delay, max. |
1.5 s |
Voltage rise, typ. |
50 ms |
Voltage increase time of the output voltage maximum |
500 ms |
Rated current value Iout rated |
20 A |
Current range |
0 ... 20 A |
● Note |
24 A up to +45°C; +60 ... +70 °C: Derating 5%/K |
Supplied active power typical |
480 W |
Short-term overload current |
|
● on short-circuiting during the start-up typical |
35 A |
● at short-circuit during operation typical |
35 A |
Duration of overloading capability for excess current |
|
● on short-circuiting during the start-up |
100 ms |
● at short-circuit during operation |
100 ms |
Parallel switching for enhanced performance |
Yes |
Numbers of parallel switchable units for enhanced performance |
2 |
Efficiency |
Efficiency at Vout rated, Iout rated, approx. |
90 % |
Power loss at Vout rated, Iout rated, approx. |
53 W |
Closed-loop control |
Dynamic mains compensation (Vin rated ±15 %), max. |
1 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
3 % |
Setting time maximum |
10 ms |
Protection and monitoring |
Output overvoltage protection |
Yes, according to EN 60950-1 |
Current limitation, typ. |
21 A |
Property of the output Short-circuit proof |
Yes |
Short-circuit protection |
Electronic shutdown, automatic restart |
Enduring short circuit current RMS value |
|
● maximum |
7 A |
Overcurrent overload capability in normal operation |
overload capability 150 % Iout rated up to 5 s/min |
Overload/short-circuit indicator |
- |
Safety |
Primary/secondary isolation |
Yes |
Galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class |
Class I |
Leakage current |
|
● maximum |
3.5 mA |
● typical |
1 mA |
Degree of protection (EN 60529) |
IP20 |
Approvals |
CE mark |
Yes |
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259, cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
Explosion protection |
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4 |
FM approval |
- |
CB approval |
Yes |
Marine approval |
DNV GL |
EMC |
Emitted interference |
EN 55022 Class B |
Supply harmonics limitation |
EN 61000-3-2 |
Noise immunity |
EN 61000-6-2 |
environmental conditions |
Ambient temperature |
|
● during operation |
0 ... 70 °C |
— Note |
with natural convection |
● during transport |
-40 ... +85 °C |
● during storage |
-40 ... +85 °C |
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
Mechanics |
Connection technology |
screw-type terminals |
Connections |
|
● Supply input |
L1, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded |
● Output |
+, -: 2 screw terminals each for 0.2 ... 4 mm² |
● Auxiliary |
13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm² |
Width of the enclosure |
115 mm |
Height of the enclosure |
145 mm |
Depth of the enclosure |
150 mm |
Required spacing |
|
● top |
50 mm |
● bottom |
50 mm |
● left |
0 mm |
● right |
0 mm |
Weight, approx. |
2.4 kg |
Product feature of the enclosure housing for side-by-side mounting |
Yes |
Installation |
Snaps onto DIN rail EN 60715 35x7.5/15 |
Electrical accessories |
Buffer module |
Mechanical accessories |
Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20 |
MTBF at 40 °C |
1 778 916 h |
Other information |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|
|