General information |
Product type designation |
DQ 16x24VDC/0.5A ST, PU 1 |
HW functional status |
From FS03 |
Firmware version |
V0.0 |
● FW update possible |
No |
usable BaseUnits |
BU type A0 |
Color code for module-specific color identification plate |
CC00 |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
Engineering with |
● STEP 7 TIA Portal configurable/integrated as of version |
V14 |
● STEP 7 configurable/integrated as of version |
V5.5 SP3 |
● PCS 7 configurable/integrated as of version |
V8.1 SP1 |
● PROFIBUS as of GSD version/GSD revision |
One GSD file each, Revision 3 and 5 and higher |
● PROFINET as of GSD version/GSD revision |
GSDML V2.3 |
Operating mode |
● DQ |
Yes |
● DQ with energy-saving function |
No |
● PWM |
No |
● Oversampling |
No |
● MSO |
No |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
19.2 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, max. |
60 mA; without load |
Output voltage |
Rated value (DC) |
24 V |
Power loss |
Power loss, typ. |
1 W |
Address area |
Address space per module |
● Address space per module, max. |
2 byte; + 2 bytes for QI information |
Hardware configuration |
Automatic encoding |
Yes |
● Mechanical coding element |
Yes |
Selection of BaseUnit for connection variants |
● 1-wire connection |
BU type A0 |
● 2-wire connection |
BU type A0 + Potential isolation module |
● 3-wire connection |
BU type A0 + Potential isolation module |
● 4-wire connection |
BU type A0 + Potential isolation module |
Digital outputs |
Type of digital output |
Source output (PNP, current-sourcing) |
Number of digital outputs |
16 |
Current-sinking |
No |
Current-sourcing |
Yes |
Digital outputs, parameterizable |
Yes |
Short-circuit protection |
Yes |
● Response threshold, typ. |
1 A; 0.7 to 1.3 A |
Open-circuit detection |
Yes |
Limitation of inductive shutdown voltage to |
Typ. L+ (-50 V) |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● with resistive load, max. |
0.5 A |
● on lamp load, max. |
5 W |
Load resistance range |
● lower limit |
48 Ω |
● upper limit |
12 kΩ |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "0" residual current, max. |
0.1 mA |
Output delay with resistive load |
● "0" to "1", typ. |
50 µs |
● "1" to "0", typ. |
100 µs |
Parallel switching of two outputs |
● for uprating |
No |
● for redundant control of a load |
Yes |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
2 Hz |
● on lamp load, max. |
10 Hz |
Total current of the outputs |
● Current per channel, max. |
0.5 A |
● Current per module, max. |
8 A |
Total current of the outputs (per module) |
horizontal installation |
— up to 30 °C, max. |
8 A |
— up to 40 °C, max. |
8 A |
— up to 50 °C, max. |
6 A |
— up to 60 °C, max. |
4 A |
vertical installation |
— up to 30 °C, max. |
8 A |
— up to 40 °C, max. |
6 A |
— up to 50 °C, max. |
4 A |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Substitute values connectable |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Monitoring the supply voltage |
Yes |
● Wire-break |
Yes; Module-wise |
● Short-circuit to M |
Yes; Module-wise |
● Short-circuit to L+ |
Yes; Module-wise |
● Group error |
Yes |
Diagnostics indication LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; Green PWR LED |
● Channel status display |
Yes; Green LED |
● for channel diagnostics |
No |
● for module diagnostics |
Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels and backplane bus |
Yes |
Isolation |
Isolation tested with |
707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety functions |
No |
Suitable for safety-related tripping of standard modules |
Yes; From FS01 |
Highest safety class achievable in safety mode |
● Performance level according to ISO 13849-1 |
PL d |
● SIL acc. to IEC 61508 |
SIL 2 |
Ambient conditions |
Ambient temperature during operation |
● horizontal installation, min. |
-30 °C |
● horizontal installation, max. |
60 °C |
● vertical installation, min. |
-30 °C |
● vertical installation, max. |
50 °C |
Altitude during operation relating to sea level |
● Installation altitude above sea level, max. |
2 000 m; On request: Installation altitudes greater than 2 000 m |
Dimensions |
Width |
15 mm |
Height |
73 mm |
Depth |
58 mm |
Weights |
Weight, approx. |
30 g |
last modified: |
05/30/2019 |