Image is illustrative
|
Simatic S7-300, Digital Output SM 322, isolated 16DO, relay contacts, 20poles Code:
6ES7322-1HH01-0AA0
Price (indicative)
€236.80
/pc
(€288.90 /pc with VAT)
Manufacturer
:
Availability:
28 days
|
Weight:
0.2835 kg/pc
|
Volume:
0.001 m3/pc
|
|
|
|
|
Simatic S7-300, Digital Output SM 322, isolated 16DO, relay contacts, 20poles, Siemens
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
120 V |
Load voltage L1 |
● Rated value (AC) |
230 V |
Input current |
from supply voltage L+, max. |
250 mA |
from backplane bus 5 V DC, max. |
100 mA |
Power loss |
Power loss, typ. |
4.5 W |
Digital outputs |
Number of digital outputs |
16; Relays |
Switching capacity of the outputs |
● on lamp load, max. |
50 W; 230 V AC |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" minimum load current |
10 mA |
Switching frequency |
● with resistive load, max. |
1 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
1 Hz |
● mechanical, max. |
10 Hz |
Total current of the outputs (per group) |
horizontal installation |
— up to 60 °C, max. |
8 A |
vertical installation |
— up to 40 °C, max. |
8 A |
Relay outputs |
● Rated supply voltage of relay coil L+ (DC) |
24 V |
● Number of operating cycles, max. |
100 000; 50 000 (24 V DC, at 2 A); 700 000 (120 V AC, at 2 A); 100 000 (230 V AC, at 2 A) |
Switching capacity of contacts |
— with inductive load, max. |
2 A; 2 A (230 V AC), 2 A (24 V DC) |
— with resistive load, max. |
2 A; 2 A (230 V AC), 2 A (24 V DC) |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Diagnostic functions |
No |
Alarms |
● Diagnostic alarm |
No |
Diagnostic messages |
● Wire-break |
No |
● Short-circuit |
No |
● Fuse blown |
No |
● missing load voltage |
No |
Diagnostics indication LED |
● Rated load voltage PWR (green) |
No |
● Fuse OK FSG (green) |
No |
● Status indicator digital output (green) |
Yes |
Potential separation |
Potential separation digital outputs |
● between the channels |
Yes |
● between the channels, in groups of |
8 |
● between the channels and backplane bus |
Yes; Optocoupler |
Isolation |
Isolation tested with |
1500 V AC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
250 g |
last modified: |
07/16/2018 |
|
File description
|