| General information |
| Product type designation |
DQ 32x24VDC/0.5A BA |
| HW functional status |
FS01 |
| Firmware version |
V1.0.0 |
| ● FW update possible |
Yes |
| Product function |
| ● I&M data |
Yes; I&M0 to I&M3 |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated as of version |
V13 / V13 |
| ● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
| ● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
| ● PROFINET as of GSD version/GSD revision |
V2.3 / - |
| Operating mode |
| ● DQ |
Yes |
| ● DQ with energy-saving function |
No |
| ● PWM |
No |
| ● Oversampling |
No |
| ● MSO |
Yes |
| Supply voltage |
| Type of supply voltage |
DC |
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes; through internal protection with 7 A per group |
| Input current |
| Current consumption, max. |
60 mA |
| Output voltage |
| Rated value (DC) |
24 V |
| Power |
| Power available from the backplane bus |
1.15 W |
| Power loss |
| Power loss, typ. |
3.8 W |
| Digital outputs |
| Type of digital output |
Transistor |
| Number of digital outputs |
32 |
| Current-sourcing |
Yes |
| Short-circuit protection |
Yes |
| ● Response threshold, typ. |
1 A |
| Limitation of inductive shutdown voltage to |
L+ (-53 V) |
| Controlling a digital input |
Yes |
| Switching capacity of the outputs |
| ● with resistive load, max. |
0.5 A |
| ● on lamp load, max. |
5 W |
| Load resistance range |
| ● lower limit |
48 Ω |
| ● upper limit |
12 kΩ |
| Output voltage |
| ● for signal "1", min. |
L+ (-0.8 V) |
| Output current |
| ● for signal "1" rated value |
0.5 A |
| ● for signal "1" permissible range, max. |
0.5 A |
| ● for signal "0" residual current, max. |
0.5 mA |
| Output delay with resistive load |
| ● "0" to "1", max. |
100 µs |
| ● "1" to "0", max. |
500 µs |
| Parallel switching of two outputs |
| ● for logic links |
Yes |
| ● for uprating |
No |
| ● for redundant control of a load |
Yes |
| Switching frequency |
| ● with resistive load, max. |
100 Hz |
| ● with inductive load, max. |
0.5 Hz; According to IEC 60947-5-1, DC-13 |
| ● on lamp load, max. |
10 Hz |
| Total current of the outputs |
| ● Current per channel, max. |
0.5 A; see additional description in the manual |
| ● Current per group, max. |
4 A; see additional description in the manual |
| ● Current per module, max. |
16 A; see additional description in the manual |
| Cable length |
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
600 m |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
No |
| Interrupts/diagnostics/status information |
| Diagnostics function |
No |
| Substitute values connectable |
No |
| Alarms |
| ● Diagnostic alarm |
No |
| Diagnostic messages |
| ● Monitoring the supply voltage |
No |
| ● Wire-break |
No |
| ● Short-circuit |
No |
| ● Group error |
No |
| Diagnostics indication LED |
| ● RUN LED |
Yes; Green LED |
| ● ERROR LED |
Yes; Red LED |
| ● Monitoring of the supply voltage (PWR-LED) |
Yes; Green LED |
| ● Channel status display |
Yes; Green LED |
| ● for channel diagnostics |
No |
| ● for module diagnostics |
No |
| Potential separation |
| Potential separation channels |
| ● between the channels |
No |
| ● between the channels, in groups of |
8 |
| ● between the channels and backplane bus |
Yes |
| Isolation |
| Isolation tested with |
707 V DC (type test) |
| Decentralized operation |
| Prioritized startup |
Yes |
| Dimensions |
| Width |
25 mm |
| Height |
147 mm |
| Depth |
129 mm |
| Weights |
| Weight, approx. |
280 g |
| Other |
| Note: |
Supplied incl. 40-pole push-in front connectors |
| last modified: |
11/10/2018 |