| General information |
| Product type designation |
AQ 2xU/I ST |
| HW functional status |
FS01 |
| Firmware version |
V1.0.0 |
| ● FW update possible |
Yes |
| Product function |
| ● I&M data |
Yes; I&M0 to I&M3 |
| ● Output range scalable |
No |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated as of version |
V13 / V13.0.2 |
| ● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
| ● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
| ● PROFINET as of GSD version/GSD revision |
V2.3 / - |
| Operating mode |
| ● Oversampling |
No |
| ● MSO |
Yes |
| CiR – Configuration in RUN |
| Reparameterization possible in RUN |
Yes |
| Calibration possible in RUN |
Yes |
| Supply voltage |
| Type of supply voltage |
DC |
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| Input current |
| Current consumption, max. |
110 mA; with 24 V DC supply |
| Power |
| Power available from the backplane bus |
0.65 W |
| Power loss |
| Power loss, typ. |
2.7 W |
| Analog outputs |
| Number of analog outputs |
2 |
| Voltage output, short-circuit protection |
Yes |
| Voltage output, short-circuit current, max. |
24 mA |
| Current output, no-load voltage, max. |
22 V |
| Cycle time (all channels), min. |
3.2 ms; independent of number of activated channels |
| Output ranges, voltage |
| ● 0 to 10 V |
Yes |
| ● 1 V to 5 V |
Yes |
| ● -5 V to +5 V |
No |
| ● -10 V to +10 V |
Yes |
| Output ranges, current |
| ● 0 to 20 mA |
Yes |
| ● -20 mA to +20 mA |
Yes |
| ● 4 mA to 20 mA |
Yes |
| Connection of actuators |
| ● for voltage output two-wire connection |
Yes |
| ● for voltage output four-wire connection |
Yes |
| ● for current output two-wire connection |
Yes |
| Load impedance (in rated range of output) |
| ● with voltage outputs, min. |
1 kΩ; 0.5 kOhm at 1 to 5 V |
| ● with voltage outputs, capacitive load, max. |
1 µF |
| ● with current outputs, max. |
750 Ω |
| ● with current outputs, inductive load, max. |
10 mH |
| Cable length |
| ● shielded, max. |
800 m; for current, 200 m for voltage |
| Analog value generation for the outputs |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
16 bit |
| ● Conversion time (per channel) |
0.5 ms |
| Settling time |
| ● for resistive load |
1.5 ms |
| ● for capacitive load |
2.5 ms |
| ● for inductive load |
2.5 ms |
| Errors/accuracies |
| Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) |
0.02 % |
| Linearity error (relative to output range), (+/-) |
0.15 % |
| Temperature error (relative to output range), (+/-) |
0.002 %/K |
| Crosstalk between the outputs, max. |
-100 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) |
0.05 % |
| Operational error limit in overall temperature range |
| ● Voltage, relative to output range, (+/-) |
0.3 % |
| ● Current, relative to output range, (+/-) |
0.3 % |
| Basic error limit (operational limit at 25 °C) |
| ● Voltage, relative to output range, (+/-) |
0.2 % |
| ● Current, relative to output range, (+/-) |
0.2 % |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
No |
| Interrupts/diagnostics/status information |
| Diagnostics function |
Yes |
| Substitute values connectable |
Yes |
| Alarms |
| ● Diagnostic alarm |
Yes |
| Diagnostic messages |
| ● Monitoring the supply voltage |
Yes |
| ● Wire-break |
Yes; Only for output type "current" |
| ● Short-circuit |
Yes; Only for output type "voltage" |
| ● Overflow/underflow |
Yes |
| Diagnostics indication LED |
| ● RUN LED |
Yes; Green LED |
| ● ERROR LED |
Yes; Red LED |
| ● Monitoring of the supply voltage (PWR-LED) |
Yes; Green LED |
| ● Channel status display |
Yes; Green LED |
| ● for channel diagnostics |
Yes; Red LED |
| ● for module diagnostics |
Yes; Red LED |
| Potential separation |
| Potential separation channels |
| ● between the channels |
No |
| ● between the channels, in groups of |
2 |
| ● between the channels and backplane bus |
Yes |
| ● Between the channels and load voltage L+ |
Yes |
| Permissible potential difference |
| between S- and MANA (UCM) |
8 V DC |
| Isolation |
| Isolation tested with |
707 V DC (type test) |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
0 °C |
| ● vertical installation, max. |
40 °C |
| Decentralized operation |
| Prioritized startup |
No |
| Dimensions |
| Width |
25 mm |
| Height |
147 mm |
| Depth |
129 mm |
| Weights |
| Weight, approx. |
200 g |
| Other |
| Note: |
Supplied incl. 40-pole push-in front connectors |
| last modified: |
03/13/2019 |