Image is illustrative
|
Signal Converter/isolator WAS4 CCC DC 4-20/4-20MA, 2-way isolator, 1-ch., input 4..20mA, output 4..20mA, 24VDC ±20%, 0..55°C, 12.5mm, Weidmüller Code:
8444980000
Price
€105.60
/pc
(€128.83 /pc with VAT)
Manufacturer
:
Availability:
21 days
|
Weight:
0.11 kg/pc
|
Volume:
0.0003 m3/pc
|
|
|
|
|
Signal Converter/Insulator WAS4 CCC DC 4-20/4-20MA, 2-way isolator, 1-ch., input 4..20mA, output 4..20mA, 24VDC ±20%, 0..55°C, 12.5mm, Weidmüller
The externally supplied ACT20M…, ACT20P… , MAS RPS/RPSH and WAS/WAZ 4/5 signal converters/ supply isolators for transmitting, isolating and converting standardised DC current signals are optionally available in widths of 6 mm (ACT20M…), 12.5 mm (WAS/WAZ4, ACT20P…) or 17.5 mm (WAS/WAZ5…). The input and output circuits and the voltage supply are completely electrically isolated. The input signal is converted into a DC current or voltage value. WAVESERIES signal converters are optionally available with a limiting frequency of 10 Hz (WAS/ WAZ4) or 20 kHz (WAS/WAZ5) for fast signal processing.
The MAS/RPS/RPSH supply isolators can supply external 2-wire sensors (ACT20P 2-/3-wire sensors) and are optionally suitable for transmitting HART protocols (MAS RPSH, ACT20P). The 24 VDC supply voltage can be cross-connected on the module side via the CH20M BUS PROFILE (ACT20M series) or using the ZQV4N (MAS) or ZQV 2.5N (WAS/ WAZ) pluggable jumpers. International approvals such as ATEX zone 2, UL C1D2 and FM Div2 also enable use in explosive risk zones.
|
|
Technical data:
|
Dimensions and weights: |
Length: 92.4 mm
Width: 12.5 mm
Depth: 112.4 mm
Net weight: 74.9 g |
Temperatures:
|
Humidity: |
40 °C / 93 % rel. humidity, no condensation |
Operating temperature: |
0 °C...55 °C |
Storage temperature: |
-20 °C...85 °C |
Input:
|
Number of inputs: |
1 |
Input current: |
4...20 mA |
Voltage drop: |
Approx. 5.6 V at 20 mA |
Output:
|
Number of outputs: |
1 |
Output current: |
4...20 mA |
Cut-off frequency (-3 dB): |
≥ 15 Hz (typ. 20 Hz) |
load impedance current: |
≤ 500 Ω |
General data:
|
Accuracy: |
± 0.2 % of final value |
Configuration: |
none |
Current consumption: |
< 32 mA @ IOUT = 20 mA |
Current-carrying capacity of cross-connect.: |
≤ 2 A |
Galvanic isolation: |
2-way isolator |
Input/Output: |
4...20 mA/ 4...20 mA |
Mounting rail: |
TS 35 |
Step response time: |
≤ 30 ms (typ. 20 ms) |
Supply voltage: |
24 V DC ± 20 % |
Temperature coefficient: |
≤ 250 ppm/K of final value |
Type of connection: |
Screw connection |
|
|
File description
|
File type
|
Download link
|
|
|
|
Product data sheet
|
PDF
|
Download link
|
|
|
|
|
|