Image is illustrative
|
DC Transducer P10, input 0..10V, output 0..10V, sv 60..300VAC/DC, DIN-rail TS35 Code:
P10-5H5HH000000M0
€140.00
/pc
(€173.60 /pc with VAT)
Manufacturer
:
|
Availability:
In Stock
|
Weight:
0.189 kg/pc
|
Volume:
0.0002 m3/pc
|
|
|
|
|
Overview
DC transducer for galvanic isolation and conversion of standard DC current or voltage signals. The input type and measurement range are selectable.
Product Features
|
Function
|
Galvanic isolation of standard DC signals
|
|
Configuration
|
Selectable input type and range
|
|
Input-to-output isolation
|
2.3kV
|
|
Supply circuit isolation
|
3.7kV
|
Input
|
Current ranges
|
0..0.1mA, 0..0.2mA, 0..0.5mA, 0..1mA, 0..2mA, 0..5mA, 0..10mA, 0..20mA, 0..40mA, 0..80mA, 0..100mA, 0.2..1mA, 1..5mA, 2..10mA, 4..20mA
|
|
Voltage ranges
|
0..50mV, 0..60mV, 0..75mV, 0..100mV, 0..200mV, 0..500mV, 0..1V, 0..2V, 0..4V, 0..5V, 0..10V, 0..15V, 0..20V, 0..24V, 0..30V, 0..36V, 0..40V, 0..48V, 0..50V, 0..60V, 0..75V, 0..110V, 0..150V, 0..200V, 0..250V, 0..300V, 0.2..1V, 1..5V, 2..10V, 4..20V
|
Output
|
Current ranges
|
0..20mA, 4..20mA
|
|
Voltage ranges
|
0..10V, 2..10V
|
|
Burden voltage
|
12V
|
|
Current output voltage limit
|
15V
|
|
Voltage output current limit
|
30mA
|
|
Residual ripple
|
Less than 0.5% p.p.
|
|
Response time
|
Less than 50ms
|
Accuracy
|
Basic accuracy
|
Less than ±0.2%
|
Power Supply
|
High auxiliary supply
|
60..300VAC or 60..300VDC, 45..400Hz
|
|
High supply power consumption
|
Less than 1.6W
|
|
Low auxiliary supply
|
24..60VAC or 24..60VDC, 45..400Hz
|
|
Low supply power consumption
|
Less than 3.4VA
|
Installation
|
Mounting
|
TS35 DIN rail, wall or mounting plate
|
|
Front protection
|
IP40
|
|
Terminal protection
|
IP20
|
Environmental Conditions
|
Operating temperature
|
-10..55°C
|
|
Storage temperature
|
-40..70°C
|
|
Relative humidity
|
Less than 75%
|
|
Altitude
|
Up to 2000m
|
Dimensions
|
Width
|
22.5mm
|
|
Height
|
65.5mm
|
|
Depth
|
106.5mm
|
|
|
|